Three-phase meter with LCD display for monitoring electric energy consumption and energy descriptions in a three-phase network, suitable for commercial and industrial applications, or for total measurement of active energy (kWh) and power (W). It features import/export kWh and W function, making it suitable for bidirectional renewable energy measurement. The meter is equipped with a reset function. The product complies with the EU directive 2014/32/EU, known as the MID - Measuring Instruments Directive.
Features:
- Manufacturer: Eastron
- Product code: SDM72B
- Excellent quality
- Compact weight and device dimensions
- Manufactured and tested according to international standards
- High measurement accuracy
- Can be used in photovoltaic installations
- Clear, backlit LCD display
- Mounting: 35 mm DIN rail
Compliance with standards:
- EN50470-1: 2006
- EN50470-3: 2006
- MID Directive 2014/32/EU
The device bears the CE conformity mark and the number of the notified body (certification number 0120/SGS0213). An additional metrological mark – the letter M and the last two digits of the year in a rectangular box – is part of the marking indicating that the measuring instrument has passed the conformity assessment according to the MID directive.
Technical parameters:
- Rated voltage: 230 / 400V AC (3-phase)
- Operating voltage: 80% - 120% Un
- Voltage withstand: AC 4kV - 1 min
- Surge withstand: 6kV - 1.2/50 μs
- Current: 10A
- Maximum rated current: 100A
- Starting current: 0.4% Ib
- Overload withstand: 30 Imax - 0.01s
- Operating frequency: 50 Hz +/- 10%
- Power consumption: 2W / 10VA / phase
- Indication: 1000 pulses/kWh
Operational parameters:
- Accuracy: class 1
- Operating temperature: -20°C / +55°C
- Storage temperature: -40°C / +70°C
- Reference temperature: +23°C +/- 2°C
- Operating humidity: 90%
- Storage humidity: 95%
- Start-up time: 10 seconds
- Degree of protection: IP51
- Mechanical environment: M1
- Protection class: II
Dimensions:
- Height: 100 mm
- Width: 72 mm
- Depth: 66 mm
Wiring diagram:
- Terminal 1/5: L1 IN / OUT
- Terminal 2/6: L2 IN / OUT
- Terminal 3/7: L3 IN / OUT
- Terminal 4/8: Neutral
Indication:
- Control display
- Software version
- Number of pulses per kWh
- Active energy consumption
- Display Type
- Digital
- Installation Type
- Rail
- Number of Phases
- Three-phase
- Maximum Current
- 100 A
Important information
Specifications are collected from official manufacturer websites. Please verify the specifications before proceeding with your final purchase. If you notice any problem you can report it here.