Lightning Protection, Type 1+2
- Connection with VDE 0185-305 (IEC 62305).
- Lightning current 12.5 kA (10/350) per pole and up to 50 kA (10/350) in total.
- Modular with screen disconnection mechanism and voltage.
- Plastic rated UL 94 V-0.
- Static transition contact for remote signaling.
- Application: Equivalent lightning current connection for buildings of category III and IV.
- Complete = Lightning rod and connection base.
Technical specifications:
- VDE approvals
- Surge current rating (8/20 µs) [total] 80 kA
- Cable type for surge protection devices: AV power cable
- Combined voltage protection level [L-PE] 2.5 kV
- Conductor cross-section, flexible (fine wire), max. 35 mm² / 2 AWG
- Conductor cross-section, flexible (fine wire), min. 1.5 mm² / 16 AWG
- Conductor cross-section, rigid (single/multi-core), max. 35 mm² / 2 AWG
- Conductor cross-section, rigid (single/multi-core), min. 1.5 mm² / 16 AWG
- Rated voltage 280V
- Lightning surge current (10/350 µs) 12.5 kA
- Max. surge protection from the network side 160 A gL/gG
- Max. continuous voltage (LN) 280 V
- Max. continuous AC voltage 280 V
- Network form TN-S, TT
- Installation location: DIN rail 35 mm
- Protection rating IP20
- SPD in EN 61643-11 Type 1+2
- Various TOV values according to the table.
- Product Number
- 5093522
- Replacement Cartridge
- No
- Maximum Discharge Current (kA)
- 12.5
Important information